⚠ For reference only. Results are estimates based on common NEC table values and must be verified against the currently adopted NEC / local code and the judgment of a licensed professional. Always confirm before installation.

Ohm's Law / Power Wheel

Enter any two values, get the other two. Leave blanks for what you want solved.

V = I × R P = V × I I = V / R P = I² × R P = V² / R

Single-Phase Power

I = (kW × 1000) / (V × PF) kVA = (V × I) / 1000

Three-Phase Power

I = (kW × 1000) / (√3 × V × PF) kVA = (√3 × V × I) / 1000

Series / Parallel Resistance

Series: Rt = R1 + R2 + … Parallel: 1/Rt = 1/R1 + 1/R2 + …

Ampacity Lookup310.16

Base ampacities per NEC Table 310.16. Temperature correction per 310.15(B)(1); adjustment for >3 conductors per 310.15(C)(1). The 60°C column applies to terminations on most equipment ≤100 A unless rated otherwise [110.14(C)].

Wire Size Selector310.16

Returns the smallest conductor whose base ampacity ≥ required current. Apply derating/correction separately for fill or high ambient.

Conduit FillCh.9 T1,4,5


Allowable fill: 1 wire = 53%, 2 wires = 31%, 3+ wires = 40% [Ch.9 Table 1]. Conductor areas per Ch.9 Table 5; conduit areas per Table 4.

Equipment Grounding Conductor250.122

Minimum equipment grounding conductor per NEC Table 250.122. If ungrounded conductors are upsized for voltage drop, the EGC must be increased proportionally [250.122(B)].

Dwelling Load Calculation (Standard)Art. 220

Standard calc per Art. 220 Part III. General lighting 3 VA/ft². First 3000 VA @100%, remainder @35% (general + small-appliance + laundry). Range demand per Table 220.55, dryer per 220.54 (min 5000 VA). HVAC at 100%, larger of heat/cool [220.60]. This is a planning estimate — verify all demand factors.

Box Fill314.16

Per 314.16(B): each conductor counts as its size's volume (Table 314.16(B)); device = 2× largest conductor; clamps/support = 1× largest; all grounds = 1× largest.

Motor Full-Load CurrentT.430.250

Three-phase induction motor FLC per NEC Table 430.250. Use table values (not nameplate) for sizing conductors and overload per 430.6(A)(1).

Voltage Drop

1Φ: VD = 2 × K × I × L / cmil 3Φ: VD = 1.732 × K × I × L / cmil K ≈ 12.9 (Cu), 21.2 (Al) Ω·cmil/ft

OCPD / Breaker Sizing240.6

Continuous loads: conductor & OCPD sized at 125% [210.20(A), 215.3]. Motor branch protection max % per Table 430.52; round up to next standard size if not exceeding the table max [240.6 standard ratings].

Conductor Derating

Adjusted = Base(90°C) × Ftemp × Fadjust (then limited by termination column)

Grounding Electrode Conductor250.66

Per NEC Table 250.66. Note exceptions: GEC to a concrete-encased electrode need not exceed 4 AWG Cu [250.66(B)]; to ground rod(s) need not exceed 6 AWG Cu [250.66(A)].